Tampere University Exam 28.4.2021
DEE-24026 Electric Power Quality

Pertti Pakonen Programmable calculator allowed 4 questions/ 4 6 p

1. Define and explain the following terms:
a) Reactive power
b) Total harmonic distortion
c) Power factor

2. a) Why shunt-connected active power filter (APF) is connected close to the industrial load?
What are the advantages and disadvantages of a series-connected APF compared to a shunt-
connected APF?

b) What are resonances in electric power networks? What happens and why when a resonance
occurs? What does resonance frequency mean and why is it relevant?

3. In what various ways standards are related to power quality and the management of
disturbances in electric power networks. Give examples of how the standards may be applied
in practice and what benefits may be achieved by them.

4. Consider a three phase short circuit occurring on one feeder of a radially operated 20 kV
distribution network supplied by a 110 kV network. The total resistance and reactance of the
supplying 110 kV network and the 110/20 kV main transformer, transformed to the 20 kV
voltage level, are 1 ohm and 5 ohm, respectively. The feeder resistance is 0.34 ohm/km and
the reactance 0.38 ohm/km. The phase-to-phase voltages in the 20 kV network before the fault
are 21 kV. .

a. draw the three phase and single phase equivalent circuits of the fault case

b. explain why and how the voltages in the network change due to the fault

c. based on calculus, illustratethe dependence of the feeder short circuit current and the
substation 20 kV busbar phase-to-phase voltage during the fault on the fault location

d. explain shortly how the changes in voltage would be different and have to be
calculated differently if the fault was a two-phase short circuit

1(1)

 


We use cookies

This website uses cookies, including third-party cookies, only for necessary purposes such as saving settings on the user's device, keeping track of user sessions and for providing the services included on the website. This website also collects other data, such as the IP address of the user and the type of web browser used. This information is collected to ensure the operation and security of the website. The collected information can also be used by third parties to enable the ordinary operation of the website.